Suitable for engineers, technicians, and more, this portable three-phase class A power quality analyzer allows you to perform diagnostics and power quality work on one, two, or three-phase networks. In addition, this analyzer features a 7" (177.8 mm) color touchscreen display, and the curve display is automatic and goes up to 10 complete cycles.
Features
Measurements
Calculations
Energy valuation
Offers all the measurements required to successfully implement energy efficiency projects and monitor electricity distribution
Shockwaves
Usually caused by lightning, are spectacular instantaneous electrical voltage surges, and they also propagate in the digital network; can withstand shockwaves up to 12 kV which are sampled every 500 ns.
Line carrier signal measurement
In the harmonic analysis function, there is also a mode for monitoring carrier currents, and after defining their frequency, the command signals will then be measured.
Interharmonics (harmonic mode)
Can be used to measure and display the interharmonics, as requested in IEC 61000-4-7, for very precise analysis of all the disturbances in an electrical network
Monitoring made easyTrend
The trend graph shows the variations of the parameters measured over time as fast as 200 ms
Alarms
Alarms set points can be programmed to be monitored, which are then recorded and time-stamped with the duration and extreme values; users can be informed directly by email when an alarm is triggered
Transients
Transients correspond to peaks in the voltage or current waveform; shockwaves are extremely fast transients with even greater possible amplitude
True InRush
For tests when starting up loads, it can record ½-period values covering more than 30 minutes and the waveforms of the signal can be captured
Versatile communicationIn addition to using media such as SD cards and USB drivers, it is possible to download the measurements and communicate with this instrument remotely via USB, remote links, Wi-Fi (direct or via server), or the RJ45 (Ethernet connector).
The web server
This analyzer is equipped with firmware for remote access. It can be controlled via VNC, which controls a remote machine while displaying its desktop. It can be activated from any browser (Chrome, Edge, Firefox, etc.).
IRD server
The IT networks are protected against external attacks. Thanks to the provision of access to the IRD server, a single authorized IP output address allows you to transmit your measurements all over the world.
SCPI commands
With an integrated interfacing software layer, it is possible to control this instrument via its own software application. SCPI commands are available for all the instrument's functions.
Data files in JSON format
Saved in JSON format, all the recordings are accessible and can be processed with a third-party and/or proprietary application.
Meeting standardsThe International Electrotechnical Commission (IEC) IEC 61000-4-30 Edition 3.1 standard. This standard defines:
The measurement parameters are described for each applicable parameter in terms that provide reliable, repeatable results, however the method is implemented.
The EN 50160 standard characterizes the quality of the voltage supplied. It presents the different types of disturbances which may affect the voltage on a network. It lists the parameters to be monitored and defines how long the parameters should be monitored for. With the DataView® software, the Monitoring mode can be used to set up a simplified configuration of all the limits to be monitored and the parameters to be recorded.
The IEC 61000-4-7 standard defines the measurement methods for voltage quality analyzers so that they remain compliant with the emission levels stipulated in certain standards (e.g. the harmonic current limits specified by IEC 61000-3-2) and for the measurement of harmonic currents and voltages on the power networks themselves.
This is caused by the power supply voltage modulation. When it affects lighting, it gives an impression of unstable vision due to a light stimulus whose luminance or spectral distribution fluctuates over time. There are two parameters calculated from the power supply voltage.
Today, electrical distribution networks are judged according to their ability to power loads causing disturbances and loads sensitive to disturbances. The latter may take multiple forms. Voltage quality analyzers can be used to detect and qualify each disturbance type: outage, voltage surges, and sags, flicker, THD, voltage variations, transients, etc.
For energy diagnostics on a site, a logger must be set up to record the electrical power and energy consumed. Once all the measurements have been taken, billing data is compared with the actual measurements to determine whether corrective action needs to be taken. This action may take different forms: resizing a transformer, implementing filtering systems, replacement of faulty equipment, etc. This analysis helps you understand and act at the right place and time to provide the best solution.
The increase in electronic power supplies in industrial processes has led to increases in harmonic disturbances on electrical networks which have a direct impact on the quality of energy distribution. These disturbances may cause failures across all the electrical devices connected to the network. Harmonic currents have negative effects on nearly all the components in the electrical system, creating new dielectric, thermal, and/or mechanical stresses.
| Inputs | 5 x voltage/4 x current, isolated |
| Voltage | 5 to 1000 V AC and V DCUnbalance (u0,u2): 0.5 to 5% (absolute); ±0.15% (absolute) |
| Mode | Harmonics: DC to 63rd order; <3% UdinInterharmonics: 0 to 62nd order; <0.5% Udin |
| Inrush and Transient Capture (Number) | No maximum (limited by SD card) |
| Shockwaves (Fast Transient) | Up to 12 kV sampled every 500 ns |
| Flicker (Pst) | <0.1 |
| Trend Recording | >900 parametersThree days with a sampling period of 200 ms15 days with a sampling period of 1 second45 days with a sampling period of 3 seconds |
| Sampling Rate | Voltage 400 kSps/current 200 kSps/surge 2 MSps |
| Alarm Mode (Types/Number) | 52/20,000 with email notifications |
| Real-Time/Power/Energy/Unbalance Modes | Yes/yes/yes/composite |
| Screenshots | No maximum (limited by SD card) |
| Carrier Current Detection | Yes |
| Data Storage | 16 GB SD-card (included) for snapshot, transients, alarms and trend recording |
| Display | 7" (177.8 mm) color LCD touch screen: 800 x 480 (WVGA) |
| Clock/GPS | Yes, built-in |
| Operating Temperature | 32 to 104°F (0 to 40°C) |
| Communication | USB, Ethernet, Wi-Fi, web server, IRD server, USB stick port (type A) |
| Compliance and Standards | Safety: IEC 61010 1000 V CAT IVEnvironmental: IEC 61557-12 and IEC 62586Measurement standard: IEC 61000-4-30 (Ed 3) Class A (Full)EN50160 monitoring mode: With PAT3 software |
| Power Supply | Battery type: Cartridge li-ion, 5800 Ah battery pack, ≤6 hours with display on; ≤10 hours with display offPower from phase from 100 to 1000 V AC/DC with external supply block |
| Dimensions | 7.87 x 11.22 x 2.17" (200 x 285 x 55 mm) |
| Weight | 4.19 lbs (1.9 kg), meter only |
All returns must be authorized. Items returned prior to authorization will not be accepted. For international customers where applicable, customers must ship any returns to us freight and duty prepaid. Return freight charges for internationsl shippments will be the responsibility of the customer.
Defective new equipment may be returned for warrantyrepair/exchange to us within (5) days of the shipment receipt date. After five (5) days, returns will be handled by direct contact and in accordance with the warranty terms of the item's manufacturer. Items that have malfunctioned due to mishandling, electrical overload, etc., will be subject to repair charge.
Non defective new equipment will be authorized for return within five (5) days of the shipment receipt date if the equipment is still in new, re-sellable condition with the original manual(s), accessories, packing material and carton. We reserve the right to reject returnsin which there is no original packaging, missing accessories, damage or visible signs of usage of the item. A restocking fee of up to 25% of purchase price may apply. Special orders and dangerous goods are non-returnable.
(Do not write anytingon the manufacturer's original package or use as a shipping carton. Include all accessories, manuals and warranties.)
Please, include a copy of the packing list or invoice with a reason for the return. Your return authorization number is valid for thirty (30) days.
We can ship to both US and Canada. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.
When you place an order, we will charge a flat rate shipping for your items.
Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.
Not Applicable
| Condition: | NA |
Defective new equipment may be returned for warrantyrepair/exchange to us within (5) days of the shipment receipt date. After five (5) days, returns will be handled by direct contact and in accordance with the warranty terms of the item's manufacturer. Items that have malfunctioned due to mishandling, electrical overload, etc., will be subject to repair charge.
Non defective new equipment will be authorized for return within five (5) days of the shipment receipt date if the equipment is still in new, re-sellable condition with the original manual(s), accessories, packing material and carton. We reserve the right to reject returnsin which there is no original packaging, missing accessories, damage or visible signs of usage of the item. A restocking fee of up to 25% of purchase price may apply. Special orders and dangerous goods are non-returnable.
(Do not write anytingon the manufacturer's original package or use as a shipping carton. Include all accessories, manuals and warranties.)
Please, include a copy of the packing list or invoice with a reason for the return. Your return authorization number is valid for thirty (30) days.