The PowerPad® III Model 8436 is a three-phase power quality analyzer that is easy-to-use, compact and shock resistant. It enables technicians and engineers to measure and carry out diagnostics and power quality work on one-, two- or three- phase networks. Five voltage and four current inputs are provided. It is IEC 61000-4-30 Class B and safety rated to 600V CAT IV. It is rated IP67 when used with the flexible sensor Ampflex® 196A.
This three-phase power quality analyzer can record 2 GB of trend data on a memory card. Additional internal memory is used to let you store alarms, transients, and snapshot data. The user can store up to 50 screen snapshots, up to 210 captured transients that contain four cycles for each active input, and >16,000 alarm events from up to 40 different parameters. Trend data can also be recorded for days, weeks, or even months. Inrush current can also be captured and stored.
Features
Applications
| Sampling Frequency | 256 samples/cycle |
| Data Storage | SD card for trend recordingAdditional separate 12.5 MB partitioned memory for snapshots, transient/inrush and alarms |
| Voltage (TRMS) | Phase-to-Phase: 2000 VPhase-to-Neutral: 1000 VVoltage Ratio: up to 500 kV |
| Current (TRMS) | MN Clamp: 0 to 6 A / 120 A or 0 to 240 ASR Clamp: 0 to 1200 AMR Clamp: 0 to 1000 Aac, 0 to 1400 AdcMiniFlex®: 10 to 3000 AAmpFlex®: 10 to 10 kA (1)SL261 Clamp: 50 mA to 100 Aac/dcJ93: 50 to 3500 Aac/dcCurrent Ratio: 10 mA to 50 kA |
| Frequency (Hz) | 40 to 69 Hz |
| Other Measurements | kW, kvar, kVA, PF, DPF, kWh, kvarh, kVAh, K-Factor, Flicker |
| Harmonics | 1st to 50th, Direction, Sequence |
| Communication Port | Optically isolated USB |
| Inputs | 4 Voltage / 4 Current |
| Sample Rate | 256 per Cycle 12.8 kHz at 50 Hz 15.36 kHz at 60 Hz |
| Vrms (AC + DC) | Range: 1000 V P to N 2000 V P to P Measurement range: 2 to 1000 V Resolution: 0.1 V Accuracy (typical): ±0.5% reading + 200 mV |
| Vpk | Range: 1414 V Measurement range: 2 to 1000 V Resolution: 0.1 V Accuracy (typical): ±3% reading + 2 V |
| Vrms Half Cycle | Range: 1000 V P to N 2000 V P to P Measurement range: 2 to 1000 V Resolution: 0.1 V Accuracy (typical): ±0.8% reading + 1 V |
| Amps (AC + DC) | Range: SR193 and MR193 Measurement range: 1 to 1000 A Resolution: 0.1 A Accuracy: ±0.5% reading + 200 mA Range: MN193 5 A Measurement range: 5 mA to 5 A Resolution: 1 mA Accuracy: ±0.5% reading + 2 mA Range: MN193 100 A Measurement range: 100 mA to 100 A Resolution: 10 mA Accuracy: ±0.5% reading + 20 mA |
| AmpFlex and MiniFlex | Range: 100 A Measurement range: 100 mA to 100 A Resolution: 10 mA Accuracy: ±0.5% reading + 30 mA Range: 6500 A Measurement range: 10 to 6500 A Resolution: 0.1 A and 1 A Accuracy: ±0.5% reading + 3 A Range: 10 kA Measurement range: 10 A to 10 kA Resolution: 1 A Accuracy: ±0.5% reading + 3 A |
| Apk | Range: SR193 and MR193 Measurement range: 1 to 1414 A Resolution: 0.1 A Accuracy: ±1% reading + 2 A Range: MN193 5 A Measurement range: 5 mA to 7.017 A Resolution: 1 mA Accuracy: ±1% reading + 20 mA Range: MN193 100 A Measurement range: 100 mA to 141.4 A Resolution: 10 mA Accuracy: ±1% reading + 200 mA |
| Apk AmpFlex and MiniFlex | Range: 100 A Measurement range: 100 mA to 100 A Resolution: 0.1 A Accuracy: ±3% reading + 600mA Range: 6500 A Measurement range: 10 to 6500 A Resolution: 0.1 A and 1 A Accuracy: ±3% reading + 5 A Range: 10 kA Measurement range: 10 A to 10 kA Resolution: 1 A Accuracy: ±3% reading + 100 A |
| A Half Cycle | Range: SR193 and MR193 Measurement range: 1 to 1200 A Resolution: 0.1 A Accuracy: ±1% reading + 10 A Range: MN193 5 A Measurement range: 5 mA to 6 A Resolution: 1 mA Accuracy: ±1% reading + 1mA Range: MN193 100 A Measurement range: 100 mA to 120 A Resolution: 10 mA Accuracy: ±1% reading + 100 mA |
| Frequency | Range: 40 to 70 Hz Resolution: 0.01 Hz Accuracy (typical): ±0.01 Hz |
| Power | Watts (VA, var) P-Q-S Probes: AmpFlex, MiniFlex Range: 10 mW to 10 MW 10 mW to 10 MW Resolution: 4 digits minimum Accuracy (typical): ±1% reading ±1.5% reading |
| Power Factor (Cos Φ/DPF) | Range: -1 to 1 Resolution: 0.001 Accuracy (typical): ±1° for Φ, +5 cts for cos Φ |
| Energy | kWh (kVAh, kvarh) P-Q-S Range: 1 mWh to 9,999,999 MWh (MVAh, Mvarh) Accuracy (typical): ±1% reading |
| Harmonics | Range: DC, 1 to 50 |
| Volts and Amp % | Range: f Measurement range: 0.0 to 1500% Resolution: 0.1% Accuracy: ±2.5% reading + 5cts Range: r Measurement range: 0.0 to 100% Resolution: 0.1% Accuracy: ±2.5% reading + 5cts Range: Absolute V Measurement range: 0 to 1000 V Resolution: 0.1 V Accuracy: ±2.5% reading + 1 V Range: Absolute A Measurement range: 0 to 1000 A Resolution: 0.1 A Accuracy: ±2% reading + 1 A Range: THD Measurement range: 0 to 999.9% Resolution: 0.1% Accuracy: ±2.5% reading + 5cts |
| Phase Angle | Range: -179° to 180° Resolution: 1° Accuracy (typical): ±1.5° + 1° × (n/12.5) |
| Additional Features | Also display Energy loss, Flicker, Plt (2H), Pst (10min), Unbalance V% and A% |
| Display | 1/4 VGA (320 x 240) color LCD display with adjustable brightness and contrast |
| Power Source | 9.6 V NiMH rechargeable battery pack (included)110 V to 1000 V DC to 400 HzBattery life: ≥8 hours with display on; ≤35 hours with display off (record mode) |
| Safety Rating | EN 61010, 600 V CAT IV(2), 1000 V CAT III, Pollution Degree 2 |
| Dimensions | 10.6 x 9.8 x 7.1" (270 x 250 x 180 mm) |
| Weight | 8.2 lbs (3.7 kg) with batteries |
All returns must be authorized. Items returned prior to authorization will not be accepted. For international customers where applicable, customers must ship any returns to us freight and duty prepaid. Return freight charges for internationsl shippments will be the responsibility of the customer.
Defective new equipment may be returned for warrantyrepair/exchange to us within (5) days of the shipment receipt date. After five (5) days, returns will be handled by direct contact and in accordance with the warranty terms of the item's manufacturer. Items that have malfunctioned due to mishandling, electrical overload, etc., will be subject to repair charge.
Non defective new equipment will be authorized for return within five (5) days of the shipment receipt date if the equipment is still in new, re-sellable condition with the original manual(s), accessories, packing material and carton. We reserve the right to reject returnsin which there is no original packaging, missing accessories, damage or visible signs of usage of the item. A restocking fee of up to 25% of purchase price may apply. Special orders and dangerous goods are non-returnable.
(Do not write anytingon the manufacturer's original package or use as a shipping carton. Include all accessories, manuals and warranties.)
Please, include a copy of the packing list or invoice with a reason for the return. Your return authorization number is valid for thirty (30) days.
We can ship to both US and Canada. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.
When you place an order, we will charge a flat rate shipping for your items.
Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.
Not Applicable
| Condition: | NA |
Defective new equipment may be returned for warrantyrepair/exchange to us within (5) days of the shipment receipt date. After five (5) days, returns will be handled by direct contact and in accordance with the warranty terms of the item's manufacturer. Items that have malfunctioned due to mishandling, electrical overload, etc., will be subject to repair charge.
Non defective new equipment will be authorized for return within five (5) days of the shipment receipt date if the equipment is still in new, re-sellable condition with the original manual(s), accessories, packing material and carton. We reserve the right to reject returnsin which there is no original packaging, missing accessories, damage or visible signs of usage of the item. A restocking fee of up to 25% of purchase price may apply. Special orders and dangerous goods are non-returnable.
(Do not write anytingon the manufacturer's original package or use as a shipping carton. Include all accessories, manuals and warranties.)
Please, include a copy of the packing list or invoice with a reason for the return. Your return authorization number is valid for thirty (30) days.