Accuenergy Acuvim-EL Series Multifunction Power and Energy Meter with DIN-rail mounting without display, 5 A/1 A input, 20 to 60 V DC
SKU: ACUVIM-EL-M-5A-P2V4
Availability: 3 to 4 Weeks Accuenergy ACUVIM-EL-M-5A-P2V4 Offers Capable of being configured as either a panel-mount device, as a DIN rail mount transducer, or installed in a pre-configured, pre-wired AcuPanel, this multifunction power and energy meter is ideal for extreme protection in even the toughest application environments. Features Revenue grade: ANSI C12.20 class 0.2 & IEC62053-22 class 0.2s 4th CT input – Measure neutral current Dual
Availability: 3 to 4 Weeks
Accuenergy ACUVIM-EL-M-5A-P2V4 Offers
Capable of being configured as either a panel-mount device, as a DIN rail mount transducer, or installed in a pre-configured, pre-wired AcuPanel, this multifunction power and energy meter is ideal for extreme protection in even the toughest application environments.
Features
- Revenue grade: ANSI C12.20 class 0.2 & IEC62053-22 class 0.2s
- 4th CT input - Measure neutral current
- Dual Ethernet ports with both RSTP bridge daisy-chain mode and separately configurable network
- Dual source meter to monitor energy usage from separate energy sources
- Data logging: Available in 8 MB onboard and offers three, assignable historical logs and a real time clock to record metering parameters with accurate timestamping (memory expandable to 8 GB with an adjustable log size)
- Designed with industry leading cybersecurity
- Modbus-RTU & BACnet MS/ TP ready
- Data logging: Offers three, assignable historical logs and a real time clock to record many metering parameters with accurate timestamping
- Individual channel configuration: Can operate as a four channel multi-circuit meter and allow CT wiring configuration through remote channel mapping
- Automatic frequency adaptation: Adjusts to local frequencies, such as 50 or 60 Hz, making it ideal in countries with differing electrical frequencies
Communication
Time of use
Display
Alarms
Power quality monitoring
Rugged, panel-mount design
Applications
- Power distribution automation
- Medium and low voltage systems
- Industrial automation
- Energy management systems
- Power quality analysis
- Electric switch gear and control panels
- Building automation
- Marine applications
Accuenergy ACUVIM-EL-M-5A-P2V4 Specifications
Specifications
| Current Inputs (Each Channel) | Nominal current options: 1: 5 A2: 1 A3: 1 A (333 mV)4: 1 A (100 mV Rope CT) Metering range:1: 0 to 10 A2: 0 to 2 A3: 0 to 1.2 A4: 0 to 1.2 A Pickup current:1: 5 mA2: 1 mA3: 5 mA4: 5 mA Withstand:20 Arms continuous, 0.1% of nominal100 Arms for 1 second, non-recurring Burden: 0.05 V A (typical) at 5 A RMS Accuracy: 0.1% at reading |
| Voltage Inputs (Each Channel) | Nominal full scale: 400 V AC L-N, 690 V AC L-L (+20%) Withstand: 1500 V AC continuous; 2500 V AC, 50/60 Hz for 1 minute Input impedance: 2 MΩ per phase Metering frequency: 45 to 65 Hz, 300 to 500 Hz Pickup voltage: 10 V ACAccuracy: 0.1% at reading |
| Energy Accuracy | Active: Class 0.2s (IEC 62053-22), Class 0.2s (ANSI C12.20)Reactive: Class 0.5 (IEC62053-24) |
| Harmonic Resolution | Metered value: 2nd to 63rd Harmonic (50 or 60 Hz type) |
| Communications | Modbus-RTU or BACnet MS/TP: Modbus-RTU2-wire shielded twisted pair cable connection 1200 to 115,200 bps |
| Control Power | Universal: AC or DCOperating Range: 100 to 415 V AC, 50/60 Hz; 100 to 300 V DC Burden: 5 W Frequency: 50/60 Hz Withstand: 3250 V AC, 50/60 Hz for 1 minuteInstallation Category III (Distribution) |
| Power | Supply: 100 to 415 V AC, 50/60 Hz, 100 to 300 V DCConsumption: 3 W |
| Environmental Conditions | Operating temperature: -13 to 158°F (-25 to 70°C)Storage temperature: -40 to 176°F (-40 to 85°C)Relative humidity: 5 to 95% non-condensing |
| Protection Level | IP56 (front), IP30 (cover) |
| Standard Compliance and Certifications | Measurement standard: IEC 62053-22, ANSI C12.20, IEC61557-12 Environmental standard: IEC 60068-2, CE, RoHS Safety standard: IEC 61010-1, UL 61010-1 EMC standard: IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, IEC 61000-3-2, IEC 61000-6-2/4 Outlines standard: DIN 43700, ANSI C39.1 Protocol conformance: IEC 61850 2nd Edition |
| Dimensions | 3.8 x 3.8 x 2" (96 x 96 x 50.7 mm)Cut-out: 3.62 x 3.62" (92 x 92 mm) or 4" (102 mm) round |
| Weight | 0.77 lbs (350 g) |
What's included with the Accuenergy ACUVIM-EL-M-5A-P2V4
- Accuenergy Acuvim-EL Series Multifunction Power and Energy Meter with DIN-rail mounting without display, 5 A/1 A input, 20 to 60 V DC
Accuenergy Acuvim-EL Series Multifunction Power and Energy Meter with DIN-rail mounting without display, 5 A/1 A input, 20 to 60 V DC. Great savings PLUS Free Shipping when you order today on EquipTestPro.com.