Accuenergy RIK 1AR Protective Relay Rogowski Coil Integrator, 0.25 to 100,000 A, 50/60 Hz
SKU: RIK 1AR
Availability: 2 to 3 Weeks Accuenergy RIK 1AR Offers Features 0 to 1 A rated output works with any protection relay or meter with a 1 A nominal current transformer input Protection class: 5P20 (IEC 61869-2) Wide current sensing range from 0.25 A to 100 kA for compatibility across any system Five field-configurable CT ratios: 50, 200, 500, 2000, and 5000 A Compatible with both 50 and 60 Hz frequency systems Easy-to-install, plug-and-play integr
Availability: 2 to 3 Weeks
Accuenergy RIK 1AR Offers
Features
- 0 to 1 A rated output works with any protection relay or meter with a 1 A nominal current transformer input
- Protection class: 5P20 (IEC 61869-2)
- Wide current sensing range from 0.25 A to 100 kA for compatibility across any system
- Five field-configurable CT ratios: 50, 200, 500, 2000, and 5000 A
- Compatible with both 50 and 60 Hz frequency systems
- Easy-to-install, plug-and-play integrator used with any protection relay, energy meter, or device with a 1 A nominal current input
- UL Listed and CE Mark
- Enclosure meets UL 94V-0 requirements
- Integrator can measure current from 0.5 to 2000% of rated current
- Industry-leading sensing range: Use on loads up to 100kA
- Plug-and-play design can be used with any device without special configuration or software
- Easy, convenient mounting on TS-35/7.5 DIN rail or inside a panel
- Fast, <100 μs settling time for full scale
Applications
- Electric power systems
- Motors
- Transformers
- Transmission lines
- Generators
- Power substations
- Utilities
- Commercial and industrial facilities
Accuenergy RIK 1AR Specifications
Specifications
| Rated Current | |
| Range | Current: 0.25 to 100,000 ASensing: 50, 200, 500, 2000, and 5000 A user selectable |
| Integrator's Current Range Settings | Primary input (Arms):5020050020005000Sensing range:0.25 to 10001 to 40002.5 to 1000010 to 4000025 to 10,0000Output:1 A at 50 A1 A at 200 A1 A at 500 A1 A at 2000 A1 A at 5000 ARelay class output:20 A at 1 kA20 A at 4 kA20 A at 10 kA20 A at 40 kA20 A at 100 kA CT ratio:50:1200:1500:12000:15000:1 |
| Integrator | Output: 0 to 1 AAccuracy: 1% at 1 A, 5% at 20 A |
| Phase Maximum Error | 1 degree |
| Class | 5P20 (IEC 61869-2) |
| Thermal Current | Continuous: 150% (1.5 A)Short-time: 20 AShort-time maximum duration: 4 seconds |
| Settling Time to Full Scale | <100 μs |
| Electrical | |
| Measurement Channels | 1 |
| Frequency Range | 50⁄60 Hz |
| Power Supply | 100 to 240 V AC |
| Burden | 0.25 Ω |
| General Specifications | |
| Input/Output Wire Connection | 14 to 30 AWG |
| Operating Temperature | Temperature: -13 to 158°F (-25 to 70°C)Humidity: Non-condensing, 0 to 95% RH |
| Integrator Enclosure Material | ABS, UL 94V-0 |
| Mounting | DIN TS-35/7.5 or 15 (DIN 43880) or Panel |
| Overload Protection | Thermal |
| Certifications | CE, UL Listed (E359521), RoHS |
| Dimensions | 7.83 x 4.93 x 4.47" (199 x 125.2 x 113.5 mm) |
| Weight | 0.8 lbs (362.9 g) |
What's included with the Accuenergy RIK 1AR
- Accuenergy RIK 1AR Protective Relay Rogowski Coil Integrator, 0.25 to 100,000 A, 50/60 Hz
Accuenergy RIK 1AR Protective Relay Rogowski Coil Integrator, 0.25 to 100,000 A, 50/60 Hz. Great savings PLUS Free Shipping when you order today on EquipTestPro.com.