AEMC 8436 PowerPad® Three-Phase Power Quality Analyzer with AmpFlex sensors, 2000 V, 10 kA
SKU: 8436 w/4 196A-24-BK
Availability: 1 to 2 Weeks AEMC Instruments 8436 w/4 196A-24-BK Offers The PowerPad® III Model 8436 is a three-phase power quality analyzer that is easy-to-use, compact and shock resistant. It enables technicians and engineers to measure and carry out diagnostics and power quality work on one-, two- or three- phase networks. Five voltage and four current inputs are provided. It is IEC 61000-4-30 Class B and safety rated to 600V CAT IV. It is r
Availability: 1 to 2 Weeks
AEMC Instruments 8436 w/4 196A-24-BK Offers
The PowerPad® III Model 8436 is a three-phase power quality analyzer that is easy-to-use, compact and shock resistant. It enables technicians and engineers to measure and carry out diagnostics and power quality work on one-, two- or three- phase networks. Five voltage and four current inputs are provided. It is IEC 61000-4-30 Class B and safety rated to 600V CAT IV. It is rated IP67 when used with the flexible sensor Ampflex® 196A.
This three-phase power quality analyzer can record 2 GB of trend data on a memory card. Additional internal memory is used to let you store alarms, transients, and snapshot data. The user can store up to 50 screen snapshots, up to 210 captured transients that contain four cycles for each active input, and >16,000 alarm events from up to 40 different parameters. Trend data can also be recorded for days, weeks, or even months. Inrush current can also be captured and stored.
Features
- Measurement of TRMS voltages up to 1000 Vrms AC/DC for two, three, four or five-wire systems
- Measurement of TRMS currents up to 10,000 Arms (sensor dependent)
- 65 μs sample rate
- With Ampflex® sensor: to measure the current flowing in a conductor or bus bar without opening the circuit and insulates the user from dangerous voltages in the circuit
- Direct measurement of neutral current and voltage
- Record and display trend data as fast as once per second for one month for up to 25 variables
- Transient detection on all V and I inputs (up to 210)
- Selectable PT and CT ratios
- Inrush current measurement
- Calculation of crest factors for V and A
- Calculation of the K-factor for transformers
- Calculation of short and long term flicker and three-phase voltage unbalance
- Measures harmonics (referenced to the fundamental or RMS value) for voltage, current or power, up to 50th harmonic
- Displays of harmonic sequencing and direction and calculation of overall harmonics
- Real-time display of phasor diagrams including values and phase angles
- Measurement of active, reactive and apparent power per phase and their respective sum total
- Calculation of power factor, displacement power factor and tangent factor
- Recording, time stamping and characterization of disturbance (swells, sags and interruptions, excedence of power and harmonic thresholds)
- 2 GB internal trend recording memory; Alarm, snapshot and transient/Inrush memories are separate
- Measurement of energy kVAh, kvarh and kWh
- The maximum and minimum RMS measurements are calculated every half-period
- Includes DataView® software for configuring, real-time display, analysis and report generation
Applications
- Power quality analysis
- Electrical diagnostics
- Energy audits
- Harmonics measurement
- Voltage and current measurement
- Power factor analysis
- Power system commissioning
- Utility services
- Renewable energy systems
- Transformer analysis
AEMC Instruments 8436 w/4 196A-24-BK Specifications
Specifications
| Sampling Frequency | 256 samples/cycle |
| Data Storage | SD card for trend recordingAdditional separate 12.5 MB partitioned memory for snapshots, transient/inrush and alarms |
| Voltage (TRMS) | Phase-to-Phase: 2000 VPhase-to-Neutral: 1000 VVoltage Ratio: up to 500 kV |
| Current (TRMS) | MN Clamp: 0 to 6 A / 120 A or 0 to 240 ASR Clamp: 0 to 1200 AMR Clamp: 0 to 1000 Aac, 0 to 1400 AdcMiniFlex®: 10 to 3000 AAmpFlex®: 10 to 10 kA (1)SL261 Clamp: 50 mA to 100 Aac/dcJ93: 50 to 3500 Aac/dcCurrent Ratio: 10 mA to 50 kA |
| Frequency (Hz) | 40 to 69 Hz |
| Other Measurements | kW, kvar, kVA, PF, DPF, kWh, kvarh, kVAh, K-Factor, Flicker |
| Harmonics | 1st to 50th, Direction, Sequence |
| Communication Port | Optically isolated USB |
| Inputs | 4 Voltage / 4 Current |
| Sample Rate | 256 per Cycle 12.8 kHz at 50 Hz 15.36 kHz at 60 Hz |
| Vrms (AC + DC) | Range: 1000 V P to N 2000 V P to P Measurement range: 2 to 1000 V Resolution: 0.1 V Accuracy (typical): ±0.5% reading + 200 mV |
| Vpk | Range: 1414 V Measurement range: 2 to 1000 V Resolution: 0.1 V Accuracy (typical): ±3% reading + 2 V |
| Vrms Half Cycle | Range: 1000 V P to N 2000 V P to P Measurement range: 2 to 1000 V Resolution: 0.1 V Accuracy (typical): ±0.8% reading + 1 V |
| Amps (AC + DC) | Range: SR193 and MR193 Measurement range: 1 to 1000 A Resolution: 0.1 A Accuracy: ±0.5% reading + 200 mA Range: MN193 5 A Measurement range: 5 mA to 5 A Resolution: 1 mA Accuracy: ±0.5% reading + 2 mA Range: MN193 100 A Measurement range: 100 mA to 100 A Resolution: 10 mA Accuracy: ±0.5% reading + 20 mA |
| AmpFlex and MiniFlex | Range: 100 A Measurement range: 100 mA to 100 A Resolution: 10 mA Accuracy: ±0.5% reading + 30 mA Range: 6500 A Measurement range: 10 to 6500 A Resolution: 0.1 A and 1 A Accuracy: ±0.5% reading + 3 A Range: 10 kA Measurement range: 10 A to 10 kA Resolution: 1 A Accuracy: ±0.5% reading + 3 A |
| Apk | Range: SR193 and MR193 Measurement range: 1 to 1414 A Resolution: 0.1 A Accuracy: ±1% reading + 2 A Range: MN193 5 A Measurement range: 5 mA to 7.017 A Resolution: 1 mA Accuracy: ±1% reading + 20 mA Range: MN193 100 A Measurement range: 100 mA to 141.4 A Resolution: 10 mA Accuracy: ±1% reading + 200 mA |
| Apk AmpFlex and MiniFlex | Range: 100 A Measurement range: 100 mA to 100 A Resolution: 0.1 A Accuracy: ±3% reading + 600mA Range: 6500 A Measurement range: 10 to 6500 A Resolution: 0.1 A and 1 A Accuracy: ±3% reading + 5 A Range: 10 kA Measurement range: 10 A to 10 kA Resolution: 1 A Accuracy: ±3% reading + 100 A |
| A Half Cycle | Range: SR193 and MR193 Measurement range: 1 to 1200 A Resolution: 0.1 A Accuracy: ±1% reading + 10 A Range: MN193 5 A Measurement range: 5 mA to 6 A Resolution: 1 mA Accuracy: ±1% reading + 1mA Range: MN193 100 A Measurement range: 100 mA to 120 A Resolution: 10 mA Accuracy: ±1% reading + 100 mA |
| Frequency | Range: 40 to 70 Hz Resolution: 0.01 Hz Accuracy (typical): ±0.01 Hz |
| Power | Watts (VA, var) P-Q-S Probes: AmpFlex, MiniFlex Range: 10 mW to 10 MW 10 mW to 10 MW Resolution: 4 digits minimum Accuracy (typical): ±1% reading ±1.5% reading |
| Power Factor (Cos Φ/DPF) | Range: -1 to 1 Resolution: 0.001 Accuracy (typical): ±1° for Φ, +5 cts for cos Φ |
| Energy | kWh (kVAh, kvarh) P-Q-S Range: 1 mWh to 9,999,999 MWh (MVAh, Mvarh) Accuracy (typical): ±1% reading |
| Harmonics | Range: DC, 1 to 50 |
| Volts and Amp % | Range: f Measurement range: 0.0 to 1500% Resolution: 0.1% Accuracy: ±2.5% reading + 5cts Range: r Measurement range: 0.0 to 100% Resolution: 0.1% Accuracy: ±2.5% reading + 5cts Range: Absolute V Measurement range: 0 to 1000 V Resolution: 0.1 V Accuracy: ±2.5% reading + 1 V Range: Absolute A Measurement range: 0 to 1000 A Resolution: 0.1 A Accuracy: ±2% reading + 1 A Range: THD Measurement range: 0 to 999.9% Resolution: 0.1% Accuracy: ±2.5% reading + 5cts |
| Phase Angle | Range: -179° to 180° Resolution: 1° Accuracy (typical): ±1.5° + 1° × (n/12.5) |
| Additional Features | Also display Energy loss, Flicker, Plt (2H), Pst (10min), Unbalance V% and A% |
| Display | 1/4 VGA (320 x 240) color LCD display with adjustable brightness and contrast |
| Power Source | 9.6 V NiMH rechargeable battery pack (included)110 V to 1000 V DC to 400 HzBattery life: ≥8 hours with display on; ≤35 hours with display off (record mode) |
| Safety Rating | EN 61010, 600 V CAT IV(2), 1000 V CAT III, Pollution Degree 2 |
| Dimensions | 10.6 x 9.8 x 7.1" (270 x 250 x 180 mm) |
| Weight | 8.2 lbs (3.7 kg) with batteries |
What's included with the AEMC Instruments 8436 w/4 196A-24-BK
- Three-Phase Power Quality Analyzer
- 4 x AmpFlex® Sensors
- 5 x 10' (3 m) Black Voltage Leads with Alligator Clips
- 5' (1.5 m) USB Cable
- 110 V US Power Cord
- 12 x Color-Coded Input ID Markers
- High-Voltage Warning/Caution Card
- NiMH Battery
- Extra-Large Tool Bag
- Accessory Pouch
- USB Drive Containing DataView® Software and User Manual
- Quick Start Guide