Megger MIT415/2 500V Insulation Tester
SKU: 1006-738
Availability: 11 to 12 Weeks12 to 13 Weeks Megger MIT415/2 Offers Replacing the BMM2000ESD, the Megger MIT415/2 Insulation Tester gives greater application range and greater functionality with simplified operation. 10 V and 100 V ESD testing 25 V & 50 V signal cable insulation testing 250 V & 500 V Insulation testing up to 50 GΩ (500 V) Continuity testing at 200 mA or 20 mA from 0.01 Ω to 999 kΩ DC and TRMS AC voltage measurement Lar
Availability: 11 to 12 Weeks12 to 13 Weeks
Megger MIT415/2 Offers
Replacing the BMM2000ESD, the Megger MIT415/2 Insulation Tester gives greater application range and greater functionality with simplified operation.
- 10 V and 100 V ESD testing
- 25 V & 50 V signal cable insulation testing
- 250 V & 500 V Insulation testing up to 50 GΩ (500 V)
- Continuity testing at 200 mA or 20 mA from 0.01 Ω to 999 kΩ
- DC and TRMS AC voltage measurement
- Large backlit display
- Combined analogue and dual digital readout
- Weatherproof to IP54
- Supplied with AA alkaline
The Megger MIT415 insulation and continuity tester is designed for electrical testing by utilities, industrial, commercial and domestic electricians. The wide range of test voltages makes the MIT415 series ideal for the engineer or technician involved with combined applications of both communications circuits and power circuits such as would be found in elevator service/repair and routine maintenance. The low test voltage insulation ranges also makes the MIT415 ideal for ESD testing.
Key Features
- CAT IV 600 V rating - provides greater safety when testing at higher voltage levels
- Adjustable insulation test voltages - provides 250 V to 1000 V or 50 V to 1000 V.
- Dual digital display readout - allows display of complimentary test information simultaneously (for example: MΩ plus test voltage or MΩ plus leakage current)
- Digital and analog arc display - includes not only the digital readout but also Megger's patented analog arc to replicate the response of a moving coil display
- Exceptional measurement range from 20 GΩ to 200 GΩ - highest insulation test range available on the market, providing a superior range of measurement applications.
- Choice of 20 mA or 200 mA continuity testing - allows user to select lower continuity range thus increasing battery life considerably
- Continuity auto-test capability - enables real two-handed operation without the need to press the test button
- Adjustable continuity limit alarm - allows pass/fail limits to be sent to speed testing
- Automatically perform PI and DAR tests - user is able to quickly perform two important diagnostic tests. . . Polarization Index (PI) and Dielectric Absorption Ratio (DAR)
- True RMS voltage measurement - allows accurate voltage measurement on noisy lines
- Auto ranging voltage measurement - automatically adjusts range from millivolts to 600 V AC or DC, eliminating the need to keep changing ranging
- Live circuit warning - automatically warns of contact to a live circuit, voltage is displayed and testing is inhibited
- Auto fuse warning - warns of fuse failure automatically. No need to test the fuse manually.
- Buzzer select button - enable or disable buzzer as required with resistance also displayed on the screen.
- Stylish tapered design and center button placement - easy to use with either hand
Specifications (MIT400-EN)
| *All quoted accuracies are at +20° C. | |
| Insulation Nominal test voltages | 250 V, 500 V, 1000 V |
| Insulation resistance range | 20 GΩ |
| Range Full Scale Accuracy | 1000 volts ±3% ±2 digits ±0.2% per GΩ 500 volts ±3% ±2 digits ±0.4% per GΩ 250 volts ±3% ±2 digits ±0.8% per GΩ |
| Analog range | 1 GΩ full scale |
| Short Circuit Current | 2 mA +0% -50% |
| Terminal voltage | -0% +20% ±1 V |
| Test Current on load | 1 mA at min. pass value of insulation specified in BS7671, HD384and IEC364, 2 mA max. |
| EN61557 Operating range | 0.10 M½ to 1.00 GΩ |
| Leakage Current | 10% ±3 digits |
| Voltage display | 3% ±3 digits ±0.5% of rated voltage |
| Polarization Index (PI) | 10 min/1 minute ratio |
| Dielectric Absorption Ratio (DAR) | 60 sec/30 sec ratio |
| Notes | (1) All ranges measure from 0.00 M½ upwards. (2) Above specifications only apply when high quality silicone leadsare being used. |
| Continuity | |
| Measurement | 0.01 ½ to 99.9 ½ (0 to 100 ½ on analog scale) |
| Accuracy | ±3% ±2 digits (0 to 100 Ω) |
| Open circuit voltage | 5 V ±1 V |
| Test current | 200 mA (–0 mA +20 mA) (0.01 ½ to 9.99 Ω) 20mA (±1 mA ) (10.0 ½ to 99.9 Ω) |
| Zero offset at probe tips | 0.10Ω typical |
| Lead resistance zeroing | Up to 9.00 Ω |
| Buzzer | Variable limit 1Ω, 2Ω, 5Ω,10Ω, 20Ω |
| Resistance | |
| Measurement | 0.01 kΩ to 1000 kΩ (0 to 1 MΩ on analog scale) |
| Accuracy | ±3% ±2 digits Open circuit voltage 5 V ±1 V Short circuit current 20 µA ± 5 µA |
| Voltage range | 0 to 600 V d.c. ±2% ±2 digits 10 mV to 600 V TRMS sinusoidal (40 to 400 Hz) ±2% ±2 digits 0 to 1000 V on Analog scale Unspecified input level 0 - 10 mV (40 to 400 Hz) For non-sinusoidal waveforms additional specification apply: ±3% ±2 digits 101 mV to 600 V TRMS and ±8% ±2 digits 10 mV to 100 mV TRMS |
| Default Voltmeter | Operates at >25 V a.c. or d.c. on any range except OFF |
| Frequency | 40 - 450 Hz (40 Hz - 99.9 Hz) ±0.5% ±1 digit (100 Hz to450 Hz) |
| Result storage | |
| Capacity | >1000 test results |
| Download | Bluetooth wireless |
| Bluetooth Class | Class II |
| Range | up to 10 m |
| Power | |
| Power Supply | 5 x 1.5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline NiMH rechargeable cells may be used. Battery life: 2200 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ |
| Dimensions | |
| Instrument | 220 x 92 x 50 mm (8.66 in. x 3.63 in. x 1.97 in.) |
| Instrument and case | 456 x 178 x 89 mm (18 in. x 7 in. x 3.5 in.) |
| Weight | |
| Instrument only | 590 gms (20.73 oz.), 775 gms (27.22 oz.) with boot |
| Instrument and case | 1.75kg (3.86 lb) |
| Fuse | Use only a 500 mA (FF) 1000 V 32 x 6 mm ceramic fuse of highbreaking capacity HBC 50 kA minimum. Glass fuses MUST NOT be fitted. |
| Safety Protection | The instruments meet EN 61010-1 (1995) to 600 V phase to earth, Category IV. Refer to safety warnings supplied. |
| E.M.C. | In accordance with IEC 61326 including amendment No.1 |
| Temperature effects | |
| Temperature coefficient | <0.1&Omega per °C up to 1 G&Omega |
| Environmental | |
| Operating range | -10 to +55° C |
| Operating humidity | 90% RH at 40° C max. |
| Storage temperature range | -25 to +70° C |
| Calibration Temperature | +20° C |
| Maximum altitude | 2000 m |
| Dust and water protection | IP54 Protected against dust and splashing water |
Applications
Industrial and Power Electrical Installation Testing
These models include all the features required for electricians, technicians and engineers working in a range of industries. Available features are selected to make testing easy and fast in a range of situations. Typical applications include:
- Building/Campus electrical maintenance
- Large and small scale electrical installations
- Periodic electrical systems inspection and testing
- Cable testing
What's included with the Megger MIT415/2
- Megger MIT415/2 500V Insulation Tester