Capable of checking mode 2 and single-phase mode 3 (level 1 and two-phase level 2) chargers, this EV charger checker can perform four EV charger safety and operation checks. In addition, this checker increases ground/earth leakage current until the protective device trips to ensure it trips at the correct leakage current level. If the leakage current that trips the device is too low, it will indicate there is an issue with the device or that there is already a high level of leakage present.
Features
Four important safety checks
Nuisance charger supply tripping check
This test will help determine whether the EV charger user is likely to experience nuisance tripping of the RCD or GFCI. This charger checker slowly increases ground/earth leakage current until the protective device trips to ensure it trips at the correct leakage current level. If the leakage current that trips the device is too low it will indicate either an issue with the device or there is already a high level of leakage present.
Four key EV charger operation checks
Applications
EVSE | Standard: IEC 61851-1:2017 Supply options (set in settings) 1. 230 V single-phase 2. 120 V single-phase 3. 208 V two-phase 4. 240 V two-phase |
Supply Measurement | Voltage Range: 5 to 300 V Resolution: 1 V Accuracy: ±5% ±2 digits Measurement: L to N, L to PE and N to PE Reverse polarity indication: L to N, for single-phase option only Frequency Range: 45 to 65 Hz Resolution: 1 Hz Accuracy: ±1 digit |
EVSE Interface (EV Charger Function) Tests | 1. Proximity detection (PP) states Read only No proximity Proximity detected, unlatched Proximity detected, latched 2. Control pilot (CP) Set and read states: State A (disconnected), State B (connected), State C (charging), State D (charging without ventilation), State E (CP short to PE) Read only state: State F - EVSE charger fault condition Maximum voltage: ±14 V Frequency: 940 to 1040 Hz Duty cycle: 8 to 97% Maximum charging current indication according to IEC 61851-1:2017, tables A.7 and A.8 |
Resistance of Earth Protective Conductor (RPE) | Test current: 200 mA Range: 0 to 10 ? Resolution: 0.01 ? Accuracy: ±5% ±2 digits |
RCD/GFCI Tests | Trip time accuracy: ±1% ±1 ms Trip current accuracy: ±3% (apply to all RCD/GFCI tests) |
Personal Protection Tests 230 V Single-Phase | 1. RCD 30 mA AC test Current: 31.5 mA AC (5% above nominal trip current) Accuracy: ±1.0 mA Maximum test time: 300 ms Polarity selection: 0 and 180° of an input sine wave 2. RCD 6 mA DC test Ramp: Up at rate of 6 mA in 2.5 seconds, then held at 6 mA DC Accuracy: ±0.5 mA Ramp polarity: Positive and negative ramp Maximum test time: 12.5 seconds Polarity selection: 0 and 180° of an input sine wave |
Personal Protection Tests 120 V Single-Phase/240 V Two-Phase | 1. GFCI/CCID 5 mA AC test Current: 6 mA AC Accuracy: ±0.5 mA Maximum test time: 5.59 seconds Polarity selection: 0 and 180° of an input sine wave 2. GFCI/CCID 20 mA AC test Current: 21 mA AC (5% above nominal trip current) Accuracy: ±0.5 mA Maximum test time: 5.59 seconds Polarity selection: 0 and 180° of an input sine wave |
Nuisance Tripping Tests 230 V Single-Phase | 1. RCD AC Ramp test Current: AC current ramp up to 30 mA in 2 mA steps Accuracy: ±0.5 mA Step time: 300 ms Maximum test time: 4.5 seconds 2. RCD DC Ramp test Test current ramp up at rate of 6 mA in 2.5 seconds, then held at 3 mA DC Maximum test time: 11.25 seconds |
Nuisance Tripping Tests 120 V Single-Phase/240 V Two-Phase | 1. GFCI/CCID 5 mA AC test Current: AC current ramp up to 6 mA in 0.5 mA steps Accuracy: ±0.5 mA Step time: 100 ms Maximum test time: 1.2 seconds 2. GFCI/CCID 20 mA AC test Current: AC current ramp up to 20 mA in 1 mA steps Accuracy: ±0.5 mA Step time: 100 ms Maximum test time: 2 seconds |
Touch Tests | Voltage: Test current typically ? of RCD nominal test current Contact pad: Dangerous voltage indication at PE conductor |
Connections | Main test: Type 2 male RPE test return: 0.157" (4 mm) shrouded socket on base of handle |
Languages | English, French, German and Spanish |
Environment Conditions | Temperature: Operating: 32 to 104°F (0 to 40°C); Storage: 14 to 158°F (-10 to 70°C) Operating humidity: 90% RH at 104°F (40°C) maximum Maximum altitude: 6561.68' (2000 m) Dust and moisture ingress: IP40 to IEC60529 in use |
Safety | Standards: IEC 61010-1:2010 EVSE standard: IEC 61851-1:2017 Category: CAT II 300 V |
Power Supply | 4 x AA cells |
Dimensions | 9.45 x 3.38 x 7.09" (24 x 8.6 x 18 cm) |
Weight | 1.28 lbs (583 g) without batteries |
EVSE | Standard: IEC 61851-1:2017 Supply options (set in settings) 1. 230 V single-phase 2. 120 V single-phase 3. 208 V two-phase 4. 240 V two-phase |
Supply Measurement | Voltage Range: 5 to 300 V Resolution: 1 V Accuracy: ±5% ±2 digits Measurement: L to N, L to PE and N to PE Reverse polarity indication: L to N, for single-phase option only Frequency Range: 45 to 65 Hz Resolution: 1 Hz Accuracy: ±1 digit |
EVSE Interface (EV Charger Function) Tests | 1. Proximity detection (PP) states Read only No proximity Proximity detected, unlatched Proximity detected, latched 2. Control pilot (CP) Set and read states: State A (disconnected), State B (connected), State C (charging), State D (charging without ventilation), State E (CP short to PE) Read only state: State F - EVSE charger fault condition Maximum voltage: ±14 V Frequency: 940 to 1040 Hz Duty cycle: 8 to 97% Maximum charging current indication according to IEC 61851-1:2017, tables A.7 and A.8 |
Resistance of Earth Protective Conductor (RPE) | Test current: 200 mA Range: 0 to 10 ? Resolution: 0.01 ? Accuracy: ±5% ±2 digits |
RCD/GFCI Tests | Trip time accuracy: ±1% ±1 ms Trip current accuracy: ±3% (apply to all RCD/GFCI tests) |
Personal Protection Tests 230 V Single-Phase | 1. RCD 30 mA AC test Current: 31.5 mA AC (5% above nominal trip current) Accuracy: ±1.0 mA Maximum test time: 300 ms Polarity selection: 0 and 180° of an input sine wave 2. RCD 6 mA DC test Ramp: Up at rate of 6 mA in 2.5 seconds, then held at 6 mA DC Accuracy: ±0.5 mA Ramp polarity: Positive and negative ramp Maximum test time: 12.5 seconds Polarity selection: 0 and 180° of an input sine wave |
Personal Protection Tests 120 V Single-Phase/240 V Two-Phase | 1. GFCI/CCID 5 mA AC test Current: 6 mA AC Accuracy: ±0.5 mA Maximum test time: 5.59 seconds Polarity selection: 0 and 180° of an input sine wave 2. GFCI/CCID 20 mA AC test Current: 21 mA AC (5% above nominal trip current) Accuracy: ±0.5 mA Maximum test time: 5.59 seconds Polarity selection: 0 and 180° of an input sine wave |
Nuisance Tripping Tests 230 V Single-Phase | 1. RCD AC Ramp test Current: AC current ramp up to 30 mA in 2 mA steps Accuracy: ±0.5 mA Step time: 300 ms Maximum test time: 4.5 seconds 2. RCD DC Ramp test Test current ramp up at rate of 6 mA in 2.5 seconds, then held at 3 mA DC Maximum test time: 11.25 seconds |
Nuisance Tripping Tests 120 V Single-Phase/240 V Two-Phase | 1. GFCI/CCID 5 mA AC test Current: AC current ramp up to 6 mA in 0.5 mA steps Accuracy: ±0.5 mA Step time: 100 ms Maximum test time: 1.2 seconds 2. GFCI/CCID 20 mA AC test Current: AC current ramp up to 20 mA in 1 mA steps Accuracy: ±0.5 mA Step time: 100 ms Maximum test time: 2 seconds |
Touch Tests | Voltage: Test current typically ? of RCD nominal test current Contact pad: Dangerous voltage indication at PE conductor |
Connections | Main test: Type 2 male RPE test return: 0.157" (4 mm) shrouded socket on base of handle |
Languages | English, French, German and Spanish |
Environment Conditions | Temperature: Operating: 32 to 104°F (0 to 40°C); Storage: 14 to 158°F (-10 to 70°C) Operating humidity: 90% RH at 104°F (40°C) maximum Maximum altitude: 6561.68' (2000 m) Dust and moisture ingress: IP40 to IEC60529 in use |
Safety | Standards: IEC 61010-1:2010 EVSE standard: IEC 61851-1:2017 Category: CAT II 300 V |
Power Supply | 4 x AA cells |
Dimensions | 9.45 x 3.38 x 7.09" (24 x 8.6 x 18 cm) |
Weight | 1.28 lbs (583 g) without batteries |
EVSE | Standard: IEC 61851-1:2017 Supply options (set in settings) 1. 230 V single-phase 2. 120 V single-phase 3. 208 V two-phase 4. 240 V two-phase |
Supply Measurement | Voltage Range: 5 to 300 V Resolution: 1 V Accuracy: ±5% ±2 digits Measurement: L to N, L to PE and N to PE Reverse polarity indication: L to N, for single-phase option only Frequency Range: 45 to 65 Hz Resolution: 1 Hz Accuracy: ±1 digit |
EVSE Interface (EV Charger Function) Tests | 1. Proximity detection (PP) states Read only No proximity Proximity detected, unlatched Proximity detected, latched 2. Control pilot (CP) Set and read states: State A (disconnected), State B (connected), State C (charging), State D (charging without ventilation), State E (CP short to PE) Read only state: State F - EVSE charger fault condition Maximum voltage: ±14 V Frequency: 940 to 1040 Hz Duty cycle: 8 to 97% Maximum charging current indication according to IEC 61851-1:2017, tables A.7 and A.8 |
Resistance of Earth Protective Conductor (RPE) | Test current: 200 mA Range: 0 to 10 ? Resolution: 0.01 ? Accuracy: ±5% ±2 digits |
RCD/GFCI Tests | Trip time accuracy: ±1% ±1 ms Trip current accuracy: ±3% (apply to all RCD/GFCI tests) |
Personal Protection Tests 230 V Single-Phase | 1. RCD 30 mA AC test Current: 31.5 mA AC (5% above nominal trip current) Accuracy: ±1.0 mA Maximum test time: 300 ms Polarity selection: 0 and 180° of an input sine wave 2. RCD 6 mA DC test Ramp: Up at rate of 6 mA in 2.5 seconds, then held at 6 mA DC Accuracy: ±0.5 mA Ramp polarity: Positive and negative ramp Maximum test time: 12.5 seconds Polarity selection: 0 and 180° of an input sine wave |
Personal Protection Tests 120 V Single-Phase/240 V Two-Phase | 1. GFCI/CCID 5 mA AC test Current: 6 mA AC Accuracy: ±0.5 mA Maximum test time: 5.59 seconds Polarity selection: 0 and 180° of an input sine wave 2. GFCI/CCID 20 mA AC test Current: 21 mA AC (5% above nominal trip current) Accuracy: ±0.5 mA Maximum test time: 5.59 seconds Polarity selection: 0 and 180° of an input sine wave |
Nuisance Tripping Tests 230 V Single-Phase | 1. RCD AC Ramp test Current: AC current ramp up to 30 mA in 2 mA steps Accuracy: ±0.5 mA Step time: 300 ms Maximum test time: 4.5 seconds 2. RCD DC Ramp test Test current ramp up at rate of 6 mA in 2.5 seconds, then held at 3 mA DC Maximum test time: 11.25 seconds |
Nuisance Tripping Tests 120 V Single-Phase/240 V Two-Phase | 1. GFCI/CCID 5 mA AC test Current: AC current ramp up to 6 mA in 0.5 mA steps Accuracy: ±0.5 mA Step time: 100 ms Maximum test time: 1.2 seconds 2. GFCI/CCID 20 mA AC test Current: AC current ramp up to 20 mA in 1 mA steps Accuracy: ±0.5 mA Step time: 100 ms Maximum test time: 2 seconds |
Touch Tests | Voltage: Test current typically ? of RCD nominal test current Contact pad: Dangerous voltage indication at PE conductor |
Connections | Main test: Type 2 male RPE test return: 0.157" (4 mm) shrouded socket on base of handle |
Languages | English, French, German and Spanish |
Environment Conditions | Temperature: Operating: 32 to 104°F (0 to 40°C); Storage: 14 to 158°F (-10 to 70°C) Operating humidity: 90% RH at 104°F (40°C) maximum Maximum altitude: 6561.68' (2000 m) Dust and moisture ingress: IP40 to IEC60529 in use |
Safety | Standards: IEC 61010-1:2010 EVSE standard: IEC 61851-1:2017 Category: CAT II 300 V |
Power Supply | 4 x AA cells |
Dimensions | 9.45 x 3.38 x 7.09" (24 x 8.6 x 18 cm) |
Weight | 1.28 lbs (583 g) without batteries |
All returns must be authorized. Items returned prior to authorization will not be accepted. For international customers where applicable, customers must ship any returns to us freight and duty prepaid. Return freight charges for internationsl shippments will be the responsibility of the customer.
Defective new equipment may be returned for warrantyrepair/exchange to us within (5) days of the shipment receipt date. After five (5) days, returns will be handled by direct contact and in accordance with the warranty terms of the item's manufacturer. Items that have malfunctioned due to mishandling, electrical overload, etc., will be subject to repair charge.
Non defective new equipment will be authorized for return within five (5) days of the shipment receipt date if the equipment is still in new, re-sellable condition with the original manual(s), accessories, packing material and carton. We reserve the right to reject returnsin which there is no original packaging, missing accessories, damage or visible signs of usage of the item. A restocking fee of up to 25% of purchase price may apply. Special orders and dangerous goods are non-returnable.
(Do not write anytingon the manufacturer's original package or use as a shipping carton. Include all accessories, manuals and warranties.)
Please, include a copy of the packing list or invoice with a reason for the return. Your return authorization number is valid for thirty (30) days.
We can ship to both US and Canada. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.
When you place an order, we will charge a flat rate shipping for your items.
Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.
Not Applicable
Condition: | NA |
Defective new equipment may be returned for warrantyrepair/exchange to us within (5) days of the shipment receipt date. After five (5) days, returns will be handled by direct contact and in accordance with the warranty terms of the item's manufacturer. Items that have malfunctioned due to mishandling, electrical overload, etc., will be subject to repair charge.
Non defective new equipment will be authorized for return within five (5) days of the shipment receipt date if the equipment is still in new, re-sellable condition with the original manual(s), accessories, packing material and carton. We reserve the right to reject returnsin which there is no original packaging, missing accessories, damage or visible signs of usage of the item. A restocking fee of up to 25% of purchase price may apply. Special orders and dangerous goods are non-returnable.
(Do not write anytingon the manufacturer's original package or use as a shipping carton. Include all accessories, manuals and warranties.)
Please, include a copy of the packing list or invoice with a reason for the return. Your return authorization number is valid for thirty (30) days.